EXTERNAL SENSOR INVENTORY,
SIGNAL DISTRIBUTION AND CABLING

new


28 Jan 99: changed the liquid flow sensors. This used to be 1 flow sensor, producing only 1 trip point. Changed to 2 sensors, providing 1 trip point and 1 analog out each.
19 July 99: The previous version was for 1/2 MVD in the full-scale mockup. I have now included all sensors on both halves, plus the chiller water sensors, and components for a third half-system to be available in the BNL clean room. 1 Feb 2000: The distribution boards got built; this fixed the pin assignments for the Relay Board.

There are a number of sensors around the MVD cooling systems.

For the whole system, that is 2 MVD halves plus sensors aroung the chillers we have:

table I
sensor -- output --
digital analog
ribbon /
connector
quantity total
channels

air flow: tmp12
+air temp: adt14
2
4
-
1
14 2×3 42

humidity: - 1 10 2×1 2

liquid temp: adt14 4 1 10 2×2+8 60

liquid flow: 1 1 10 2×2 8

liquid level: - 1 10 2×1 2

total field sensors / channels: 26 114

All 114 channels are carried to the sensor distribution boards, but only a subset of those will be read out, and an overlapping subset will be used to switch the relay boards.

 

table II
sensor
East      West
sensor location # active
leads
length (m)
East      West
T1F1 T6F6 heat exchange box
plenum air out
14 7.5 7.5
T2F2 T7F7 1m below MVD,
plenum return
14 4.5 4.5
T3F3 T8F8 1m below MVD,
volume return
14 4.5 4.5
spare spare   14    
H1 H2 in fan housing 3 7.5 7.5
L1 L2 in heat exch. box 3 7.5 7.5
T4 T9 just below MVD North 7 7.0 7.5
T5 T10 just below MVD South 7 7.0 7.5
F9 F4 near liquid pump out 5 7.5 8.0
F10 F5 near liquid pump in 5 7.0 7.5
T15   building water supply
on chiller #1
7 8.0 -
T16   building water return
on chiller #1
7 8.0 -
T17 T11 chiller #1(3)
liquid supply
7 8.0 4.0
T18 T13 chiller #2(4)
liquid supply
7 7.0 8.0
  T12 chiller #1
liquid return
7 8.0 -
  T14 chiller #2
liquid return
7 - 8.0
           
RS232 RS232 chiller #1(3) control ?? 8.0 4.0
RS232 RS232 chiller #2(4) control ?? 7.0 8.0
control control chiller #1(3) 1 8.0 4.0
control control chiller #2(4) 1 7.0 8.0
control control fan 1 7.5 7.5
control control pump 1 7.5 7.5

The 4.65 number coms from looking up the longest cable run from the motherboard to the rack, and subtracting 1m. In addition, we need 2 short 34-pin ribbons to go from the distribution board to the ADC module, and one short 40-pin ribbon from the distribution board to the relay board.


The sensor cables arrive at the ancillary crate, where some of the signals need to be routed to the relay board, and some to the custom ADC module. In addition, the sensor cables are also used to carry power from the crate to the field sensors. To route the signals and power in a well-organized, reconfigurable fashion, we need sensor distribution boards, as shown here:

Postscript version







Sensor Distribution Boards
These are the 'sensor distribution modules', two identical double-wide 6U VME board, with front panel assignment as indicated. The sensor names (Tx, Fx, Hx) correspond to the nomenclature on this schematic of the cooling systems.

postscript version ->

All the details of the distribution boards are here.


Parts list for distribution boards

This is on the assumption that we'll have 2 boards + 1 spare:

table III
part quantity we have need comments
14-pin RH 6 - 6 makes
1 condo
14-pin straight 6 14 -
10-pin RH 18 - 18 makes
1 condo
10-pin straight 18 - 18
32-pin RH 3 - 3 makes
1 condo
32-pin straight 3 - 3
40-pin RH 3+18 1 20  
VME backplane 6 lots -  

Field Sensors

Here is the schematic of the little [TxFx] sensor board, in gif or postscript. This sensor combination sits in the airflow.
Here is the ADT14 chip and the TMP12 chip pinouts.
to ADC? to relay?
Pin assignment for the [TxFx] sensors: 1 power - -
2 ground - -
3 power - -
4 ground - -
5 power - -
6 ground - -
7 low-low temperature trip - -
8 low T trip - -
9 high T trip x -
10 high-high T trip x x
11 analog temperature x -
12 - - -
13 low flow trip x -
14 high flow trip x x


Here is the schematic of the little [Tx] sensor board, in gif or postscript. These sit on short copper sections in the liquid circuits.

to ADC? to relay?
Pin assignment for the [Tx] sensors: 1 power
  • 2 ground - -
    3 low-low temperature trip - -
    4 low T trip - -
    5 high T trip x -
    6 high-high T trip x x
    7 analog temperature x -
    8 - - -
    9 - - -
    10 - - -


    Here is the schematic of the little [Fx] sensor board, in gif or postscript.

    to ADC? to relay?
    Pin assignment for the [Fx] sensors: 1 power - -
    2 ground - -
    3 low flow trip x x
    4 analog out x -
    5-10 NC - -


    to ADC? to relay?
    Pin assignment for the [Hx] sensor:
    1 power - -
    2 ground - -
    3 analog humidity x -
    4-10 NC - -


    to ADC? to relay?
    Pin assignment for the [Lx] sensor:
    1 power - -
    2 ground - -
    3 analog liquid level x -
    4-10 NC - -



    Parts list for field sensors

    For the '# of sets' (one set per MVD half) I assume we need to be able to provide services for 3 MVD halves (2 in the hall and 1 in the BNL cleantent), plus spares.

    table IV
    parameter sensor other parts # of sets
    air temperature ADT14 100K pot (2), 50K pot (2), 14-pin conn, 10K R (4) testpoints (4), 16-pin socket? (1). 3×3+2
    air flow TMP12 500K pot (2), no conn, 10K R (2) testpoints (2), 8-pin socket? (1). 3×3+2
    air humidity Omega HX49? 10-pin conn. 3×1+1
    drain water Omega LV170 10-pin conn, xx? 3×1+1
    liquid temp ADT14 100K pot (2), 50K pot (2), 10-pin conn, 10K R (4) testpoints (4), 16-pin socket? (1). 3×2+2
    liquid flow Omega xxx 200K R (1), 100K R (1), 10-pin conn. 3×1+1
    chiller temperatures ADT14 100K pot (2), 50K pot (2), 10-pin conn, 10K R (4) testpoints (4), 16-pin socket? (1). 8+6+2

    table V
    part quantity we have need comments
    ADT14 19 3 16  
    TMP12 11 7 4  
    Omega-HX49 4 1? 3? bad hum sensor
    Omega-LV170 4 1 3  
    Omega-xxx 4 1 3  
    R 10K 162 1000 -  
    R 100K 4 1000 -  
    R 200K 4 1000 -  
    pot 50K 70 22 48 can recover a few
    pot 100K 70 2 68 can recover a few
    pot 500K 22 4 18 can recover a few
    14-pin conn 11 12 -  
    10-pin conn 36 20 16  
    testpoints 162 1000 -  
    16-pin socket 35 14 21  
    8-pin socket 11 - 11  


    ADC channels
    The ADC channels are in the table below. The order follows that of the sensor distribution boards. Since there are only 32 channels per side available, not all of the channels are read out - non-essential ones are dropped. A netlist is here.

    table VI
    -----East-----
    sensor signal ADC
    channel
    relay
    brd.

    T1 low-low - -
      low - -
      high 1 -
      high-high 2 1
      analog 3 -
    F1 low 4 2
      high 5 -
    T2 low-low - -
      low - -
      high 6 -
      high-high 7 3
      analog 8 -
    F2 low 9 4
      high 10 -
    T3 low-low - -
      low - -
      high 11 -
      high-high 12 5
      analog 13 -
    F3 low 14 6
      high 15 -
    H1 analog 17 -
    L1 analog 18 -
    T4 low-low - -
      low - -
      high 19 -
      high-high 20 7
      analog 21 -
    T5 low-low - -
      low - -
      high 22 -
      high-high 23 8
      analog 24 -
    F4 low 25 9
      analog 26 -
    F5 low 27 10
      analog 28 -
    T11 low-low - -
      low - -
      high - -
      high-high - -
      analog 29 -
    T12 low-low - -
      low - -
      high - -
      high-high - -
      analog 30 -
    T13 low-low - -
      low - -
      high - -
      high-high - -
      analog 31 -
    T14 low-low - -
      low - -
      high - -
      high-high - -
      analog 32 -
    -----West-----
    sensor signal ADC
    channel

    T6 low-low - -
      low - -
      high 33 -
      high-high 34 11
      analog 35 -
    F6 low 36 12
      high 37 -
    T7 low-low - -
      low - -
      high 38 -
      high-high 39 13
      analog 40 -
    F7 low 41 14
      high 42 -
    T8 low-low - -
      low - -
      high 43 -
      high-high 44 15
      analog 45 -
    F8 low 46 16
      high 47 -
    H2 analog 49 -
    L2 analog 50 -
    T9 low-low - -
      low - -
      high 51 -
      high-high 52 17
      analog 53 -
    T10 low-low - -
      low - -
      high 54 -
      high-high 55 18
      analog 56 -
    F9 low 57 19
      analog 58 -
    F10 low 59 20
      analog 60 -
    T15 low-low - -
      low - -
      high - -
      high-high - -
      analog 61 -
    T16 low-low - -
      low - -
      high - -
      high-high - -
      analog 62 -
    T17 low-low - -
      low - -
      high - -
      high-high - -
      analog 63 -
    T18 low-low - -
      low - -
      high - -
      high-high - -
      analog 64 -
    ADC channels 16 and 32 are unused.
    Note that on the connectors channels 1 and 17 are at the bottom.




    Parts list for cables
    table VII
    part quantity we have need comments
    14-pin f 24 some incomplete? assemblies 24?  
    10-pin f 72 - 72  
    cable 14-lead, 5m 8+4 300 ft -  
    cable 10-lead, 5m 24+12 - 400+200'  
     
    RS-232 f?/m? 6+2 ? 8?  
    cable xxx-lead, 5m 3+1 ? 60'  



    The relay board channel assignment is as follows:
    1 T1 air
    2 F1
    3 T2
    4 F2
    5 T3
    6 F3
    7 T4 liquid
    8 T5
    9 F4
    10 F5


    Last update 20 April 2001 - Hubert