Since the RHIC Engineering Run in 1998, several issues have surfaced
that make the current setup
less suitable for MVD's purpose.
A. Current setup
There are four pin-diode modules
on each of the PHENIX nosecones,
for a total of eight.
The powers and output signals to each module are carried by a ribbon
cable that connects to
the module via 10-pin connector. The ribbon goes to a passive
junction box located on top
of a cable tray on top of the Beam-Beam Counter rack on the west side
of PEH. The junction
box is connected to the counting house by a multi-conductor copper
cable that runs 150-plus
feet in length. This cable carries both powers and signals, and
is 150-plus feet in length.
In the counting house, the cable is connected to a power supply/signal
junction box.
This box was located in the RHIC Controls Rack, and was powered by
the 208VAC.
The signal from a pin-diode module was simply fed into a discriminator
so that it would
give a NIM logic signal whenever the pin-diodes were hit. The
NIM signal was fed into
either a visual scaler or the RHIC's scaler readout system. Four
of the eight modules were
instrumented in this fashion.
STAR Experiment has a similar setup, except their power supply/signal
junction box sits
in the experimental hall behind the shielding. Also, their signal
gets converted to optical signal
at the junction box, and goes to their counting house, where it gets
converted back to logic
signal and fed into the RHIC scaler readout system.
B. Problems with the current setup
The power supply sitting in the counting house is not configured to
satisfy the RHIC safety requirements.
During the Engineering Run, the radiation monitoring system was given
a go-ahead since it was
virtually identical to the STAR's system, and that was RHIC-approved.
After the ER, however,
closer scrutiny of the power supply by RHIC determined that it is not
OK. The fact that STAR'r
power suppy is OK may have to do with the fact that STAR's power supply
sits inside the shielding
while ours sits in the counting house, where there is lot more people
traffic.
The power supply itself is not reliable. While we did not have
the power supply turned on long
enought to notice any failures, the STAR's was, and they had problems.
And the power supply
being behind the shielding makes any fix impossible while the interaction
region (IR) is secure.
Connecting the IR to the counting house with copper is a big no-no due
to ground loop problems.
Thus, an optical link must be installed. This means that analog-to-optical
junction must be made
in the IR, and reverse in the counting house for eight channels.
Optical fibers (8) must also be laid
between the IR and the counting house.
Readout and archiving of the signals might be a problem. RHIC
Controls does have a readout
system in place to read the scaler readings from the Zero-Degree
Calorimeter (ZDC). However,
during the ER, the readouts were not archived for later analysis.
It is not clear at this moment whether
RHIC plans to do this or not. For MVD, recorded data with time
stamps are critical in order to gauge
the radiation danger for the detector.
C. Proposal
Given the problems listed above, I propose the following idea.
It's actually the original idea that we
considered -- and that is, make the radiation monitor be part of the
MVD ancillary system. By this I
mean utilizing the powers available to the ancillary system, and also
use the readout system. The pin-diode
modules are very simple to operate. Each module requires +5VDC
(~45mA), -5VDC (~72mA),
and +25VDC (~4mA) for power. The output signal is a positive
TTL (50 ohm). Both powers and
signal are carried to and from the module via 10-pin ribbon cable.
I propose that the +25VDC power be tapped out from the MVD
High-Voltage system. A full MVD requires
4 LeCroy 1461P-M410 modules, and we have 6 total. Each module
has 12 independent channels. The
1461P variant M410 has a current limit of 0.256 mA, far less than the
required 4 mA for the +25VDC.
The 1461P module, however, can be reconfigured to provide higher currents
to satisfy the 4 mA
requirements. The power can be derived directly from the LeCroy
crate, or from the HV distribution
crate.
The +5VDC and -5VDC can be tapped out of the MVD Low-Voltage
system. These powers can
be derived from the LV distributiion crate.
The readout will be done along with all the other MVD
ancillary readouts. Appropriate VME module
will have to be found, that will allow scaler values to be converted
to ADC or read out directly.
The big advantage of this proposal is that everything resides in the
MVD ancillary crate, close to the
nosecones where the pin-diodes are located. The cabling of these
modules can also be bundled
together with the other MVD cables. The other advantage is that
the system will be totally under the
MVD control without having to rely on other systems for readout or
power.