 For chillers #2 and #4:
 
     
      Go to the PC in the 1008 Rack Room. There is a terminal where it says
'HV OPC' in this (old - 2001) drawing:
       Choose channel 4 on the 'Raritan KVM switch port, on the lower 
           right. This connects the screen to phoncs8, which is the PC where
           OPC-A runs, among other things. 
      Go to Start -> Programs -> Accessories -> 
       Communications -> Hyperterminal.
       MVD-com25.ht is chiller 2, and MVD-com27 is chiller 4. 
       to disconnect, simply close the window.
       (contact: Steve Boose)
     
 For chiller #3:
 
    This port got connected to a terminal server in the IR. 
         
      Go to any terminal, log in on phoncs0, and type:
        ts mvdchiller3. This opens a terminal window to the chiller.
 Type in UPPER CASE. This one is picky.   
       to disconnect, type <CTRL>], and quit telnet. 
       (contact: John Haggerty) 
     
 For chiller #1:
 
    This chiller has a broken rs232 port. It is connected to the PC,
    with MVD-com24, but does not respond.
    
 
 |   |